Change Effect of LCL Filter Parameter Values and Series Damping Resistor Value in Single Phase Grid Connected Inverter

Abstract
In this study, LCL filter parameters of a single phase grid connected inverter were calculated. The change of total harmonic distortion (THD) of the grid current and power loss values when the calculated LCL filter parameters and series damping resistor were increased and decreased by 50% was analyzed and the most appropriate values were determined. Analysis studies were carried out using the PSIM simulation program. The study had a power of 1 kW and proportional resonant (PR) control was used in current control and T/4 delay PLL structure was used in PLL algorithm. According to the results of the analysis, it was determined that increasing the inductor values decreased the THD value of the current and the amount of power loss. In addition, decreasing the damping resistor value also decreased THD and power loss values. In LCL filter design, it was seen that it would be appropriate to increase the inductor values and to decrease the series damping resistor value.
Description
Keywords
LCL filter, Single phase grid connected inverter, PR current control